shaft synchronization application – parameter lists vacon • 27
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
6
SHAFT SYNCHRONIZATION SPECIFIC PARAMETERS
P2.6.20
Response to
position error
0 3 2
1730 See P2.6.17
P2.6.21
Position error
threshold
0
2147483647
u 3932160
1731
Threshold for position
error during
synchronization
P2.6.22
Power unit
temperature sensor
supervision
0 1 0
1732
0=Read
1=Ignore
P2.6.23
Encoder
supervision
0 1 0
1733
0=Enabled
1=Disabled
P2.6.24 Lock Response 0 3 2 1734 See P2.6.17
P2.6.25
Lock Freq Diff 0,00 Par. 2.1.2 Hz 2,00
1735
Allowed difference
between output
frequency and the
encoder feedback
frequency
P2.6.26
Lock fault delay 0,00 10,00 s 0,50
1736
If freq. difference is
higher than ID1735 in this
time the lock fault is
triggered
P2.6.27 Disable stop lock 0 1 0
1086
Only for Vacon personnel.
Possibility to change
parameters in run state
when this parameter is
set to 1.
Table 20. Protections, G2.6