6. Modbus Communication
Transmitters ordered with the Modbus configuration option are accessed using the Modbus
serial communication protocol. The supported Modbus variant is Modbus RTU (Serial Modbus)
over RS-485 interface.
The supported Modbus functions and registers are described in Modbus Reference
(page 75).
The following table lists the default Modbus serial settings of devices ordered with the Modbus
configuration option.
Table 6 Default Modbus Serial Communication Settings
Description Default Value
Serial bit rate 19200
Parity N
Number of data bits 8
Number of stop bits 2
Modbus device address 240
Serial delay 0
Communication mode Modbus RTU
Use Vaisala Insight software to change the Modbus serial communication settings if needed.
More Information
Vaisala Insight Software (page 36)
DMT143 User Guide M211435EN-J