7.4 Current Transformer Selection
VAMP 24h support phone +358 (0)20 753 3264
Marking:
Accuracy limit factor is written after the accuracy class.
E.g. 10 VA 5P10, 15 VA 10P10, 30 VA 5P20.
The actual accuracy limit factor k
A
depends on the actual
burden.
Equation 7.4.1-3.
Accuracy limit factor at rated current and rated burden
Internal secondary burden. (Winding resistance R
CT
in Figure
7.4.1-1)
Actual burden including wiring and the load.
Figure 7.4.1-2 This figure of Equation 7.4.1-3 shows that it is essential to
know the winding resistance R
CT
of the CT if the load is much less than the
nominal. A 10 VA 5P10 CT with 25% load gives actual ALF values from
15..30 when the winding resistance varies from 0.5 to 0.05 .