7.9 Trip Circuit Supervision
VAMP 24h support phone +358 (0)20 753 3264
Example of dimensioning the external resistor R:
110 Vdc –5 % + 10%
Auxiliary voltage with tolerance. Short time voltage
dips more than 5 % are not critical from the trip
circuit supervision point of view.
Relay type for the K1 auxiliary relay:
Phoenix Contact 2941455
EMG 17-REL/KSR-120/21-21-LC Au
120 Vac/dc –20 % + 10%
Coil voltage of the auxiliary relay K1
6 mA
Nominal coil current of the auxiliary relay K1
50 W
Rated power of the open coil of the circuit breaker.