Engineer programming via the keypad
16
Timers
115
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
Timer
Description
Default
FINAL EXIT
is closed. (1 – 45 seconds)
Bell on Fullset
FULLSET BELL
Activates the external bell momentarily to indicate a full set
condition. (0 – 10 seconds)
0 sec.
Strobe on Fullset
FULLSET STROBE
Activates the strobe on the external bell momentarily to
indicate a full set condition. (0 – 10 seconds)
0 sec.
Fail To Set
FAIL TO SET
Number of seconds to display fail to set message on keypads
(0 until valid PIN is entered). (0 – 999 seconds)
10 sec.
Alarm
Double Knock
DKNOCK DELAY
The maximum delay between activation’s of zones with the
double attribute, which will cause an alarm. (1 – 99 seconds)
10 sec.
Soak
SOAK DAYS
The number of days a zone remains under soak test before it
automatically returns to normal operation. (1 – 99 days)
14 days
Seismic Test Interval
SEISMIC AUTOTEST
The average period between seismic sensor automatic tests
(12 – 240 hours)
Note: To enable automatic testing, the Automatic Sensor Test
attribute must be enabled for a seismic zone.
168 hours.
Seismic Test Duration
SEISMIC TEST DUR
Maximum time (in seconds) that a seismic sensor takes to
trigger an alarm in response to the 'Seismic Test' output.
(3 - 120 seconds)
30 sec.
Lockout Post Alarm
LOCKOUT POST
ALARM
Duration after alarm that access will be denied.
0 mins
External Bell Strobe
STROBE TIME
Duration that the strobe output will be active when an alarm is
activated. (1 – 15 minutes; 0 = indefinitely)
15 min.
Alerts
Mains Delay
MAINS SIG DELAY
The time after a mains fault has been detected before an alert
is activated by the system. (0 – 60 minutes)
0 min.
Engineer
Engineer Access
ENGINEER ACCESS
The timer for the Engineer access starts as soon as the user
enables the Engineer Access. (0 – 999 minutes. ‘0’ indicates
no time limitation for system access)
0 min.
Engineer auto log out
ENG AUTO LOG OUT
Duration of inactivity after which the engineer will be
automatically locked out
0 mins.
Keypad
Keypad Timeout
KEYPAD TIMEOUT
The number of seconds that an RKD will wait for key entry
before it leaves the current menu. (10 – 300 seconds)
30 sec.
Keypad Language
KEYPAD LANGUAGE
The duration a keypad will wait in idle before switching
language to default ( 0 - 9999 seconds; 0 = never).
10 secs
Fire
Fire Pre-alarm
FIRE PRE-ALARM
Number of seconds to wait before reporting fire alarm for
zones with ‘Fire pre-alarm’ attribute set. (1 – 999 seconds)
See Editing a Zone [âž™ 237].
30 sec.
Fire recognition
FIRE RECOGNITION
Extra time to wait before reporting file alarm for zones with
‘Fire pre-alarm’ and ‘Fire Recognition’ attributes set. (1 – 999
seconds). See Editing a Zone [âž™ 237].
120 sec.
PIN
PIN Valid
PIN VALID
Period for which pin is valid in days ( 1 - 330 )
30 days
PIN Changes Limit
PIN CHANGES LIMIT
Number of changes within a valid period ( 1 - 50 )
5
PIN Warning
PIN WARN
Time before PIN expiry after which a warning will be
displayed
( 1 - 14 )
5 days