Model GXT5 750IRT2UXL 750IRT2UXLE 1000IRT2UXL 1000IRT2UXLA 1000IRT2UXLE
Rating 750 VA/750 W 1000 VA/1000 W
Environmental Requirements
Operating Temperature, °F (°C) Operation temperature (full rating): 32 to 104 (0 to 40)
Extended Operating Temperature, °F (°C) 32 to 122 (0 to 50); output derated by 1% per 1 °C above 40 °C
Storage Temperature, °F (°C)
5 °F to 122 °F (-15 °C to 50 °C)
( contain batteries will be from -15 to 40 °C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000 m) at 77 °F (25 °C) without derating
Audible Noise <46 dBA max at 3 ft. (1 m) front and sides <43 dBA max at 3 ft. (1 m) rear
Agency
Safety 1 IEC 62040-1:2008+A1
EN 62040-
1:2008+A1:2013; GS
mark; UL 1778 5th
Edition and CSA
22.2 No.107.3
EMC EN 62040-2:2006 EN 61000-3-2:2014 EN 61000-3-3:2013 -
EN 62040-2:2006
EN 61000-3-2:2014
EN 61000-3-3:2013
Transportation ISTA Procedure 1A - ISTA Procedure 1A
Surge Immunity ANSI C62.41 Category B IEC 61000-4-5 -
ANSI C62.41
Category B IEC
61000-4-5
RFI/EMI CISPR22 Class A - CISPR22 Class A
*For GXT5-1000IRT2UXL—The product fulfils the requirement of IEC 62040-1: 2017+A1:2021, AS 62040.1:2019, EN IEC 62040-1:2019+A11:2021 and BS EN
IEC 62040-1:2019+A11:2021.
Table 8.1 UPS Specifications, 750 VA and 1000 VA Models (continued)
Model GXT5 1500IRT2UXL 1500IRT2UXLA 1500IRT2UXLE 2000IRT2UXL 2000IRT2UXLA 2000IRT2UXLE
Rating 1500 VA/1500 W 2000 VA/2000 W
Dimensions, D×W×H, in. (mm)
Unit 18.5×16.9×3.4 (470×430×85)
Shipping 24.3 ×22.4 x 10.3 (617 x 570 x 262)
Weight, lb.(kg)
Unit 46.2 (21) 56.1 (25.5) 61.6 (28) 56.1 (25.5)
Shipping 61.6 (28)
Input AC
Voltage (typical) 230 VAC nominal; variable based on output load
Table 8.2 UPS Specifications, 1500 VA and 2000 VA Models
86 Proprietary and Confidential ©2024 Vertiv Group Corp. 8 Specifications
Vertiv™ Liebert® GXT5 UPS Installer/User Guide