Model GXT5 1500IRT2UXL 1500IRT2UXLA 1500IRT2UXLE 2000IRT2UXL 2000IRT2UXLA 2000IRT2UXLE
Rating 1500 VA/1500 W 2000 VA/2000 W
90% to 100%
loading
168 to 288 VAC
70% to 90%
loading
150 to 288 VAC
50% to 70%
loading
115 to 288 VAC
0 to 50% loading 115 to 288 VAC
Frequency 40 Hz to 70 Hz; Auto Sensing
Input Power
Cord
C14 C20
Output AC
Output
Receptacles
C13×8 IRAMx3 C13×8 C13×8 C13x6 C13×8
Voltage 200/208/220/230/240 VAC (user-configurable); ±3%
Waveform Sine wave
Utility (AC)
Model Overload
>200% for 250 ms 150-200% for 2 seconds 125-150% for 50 seconds 105-125% 60 seconds
Internal Charger
Charging current Nominal 1.8 A; Maximum 8 A
Battery
Type Valve-regulated, non-spillable, lead acid
Qty×V×Rating 4 × 12V × 9.0 Ah
Backup time See Battery Run Times on page99.
Recharge Time 4 Hours to 90% capacity after full discharge with 100% load until UPS auto-shutdown (Internal Batteries Only)
Table 8.2 UPS Specifications, 1500 VA and 2000 VA Models (continued)
8 Specifications Proprietary and Confidential ©2024 Vertiv Group Corp. 87
Vertiv™ Liebert® GXT5 UPS Installer/User Guide