Model GXT5 1500IRT2UXL 1500IRT2UXLA 1500IRT2UXLE 2000IRT2UXL 2000IRT2UXLA 2000IRT2UXLE
Rating 1500 VA/1500 W 2000 VA/2000 W
Environmental Requirements
Operating
Temperature, °F
(°C)
Operating temperature (full rating): 32 to 104 (0 to 40)
Extended
Operating
Temperature, °F
(°C)
32 to 122 (0 to 50); output derated by 1% per 1 °C above 40 °C
Storage
Temperature, °F
(°C)
-4to +140 (-20 to 60) ( contain batteries will be from -15 to 40 °C.)
Relative
Humidity
0% to 95%, non-condensing
Operating
Elevation
Up to 10,000 ft. (3000 m) at 77ºF (25ºC) without derating
Audible Noise
<46 dBA max at 3 ft. (1 m) front and
sides <45 dBA max at 3 ft. (1 m) rear
<48 dBA max at 3 ft. (1 m) front and
sides <48 dBA max at 3 ft. (1 m) rear
Agency
Safety
EN 62040-
1:2008+A1:2013;
GS mark; UL 1778
5th Edition and
CSA 22.2 No.107.3
IEC 62040-
1:2008+A1
EN 62040-1:2008+A1:2013; GS mark; UL
1778 5th Edition and CSA 22.2 No.107.3
IEC 62040-
1:2008+A1
EN 62040-
1:2008+A1:2013; GS
mark; UL 1778 5th
Edition and CSA
22.2 No.107.3
EMC
EN 62040-2:2006
EN 61000-3-
2:2014 EN 61000-
3- 3:2013
-
EN 62040-2:2006 EN 61000-3-2:2014 EN
61000-3-3:2013
-
EN 62040-2:2006
EN 61000-3-2:2014
EN 61000-3-3:2013
Transportation ISTA Procedure 1A - ISTA Procedure 1A - ISTA Procedure 1A
Surge Immunity
ANSI C62.41
Category B IEC
61000-4-5
- ANSI C62.41 Category B IEC 61000-4-5 -
ANSI C62.41
Category B IEC
61000-4-5
RFI/EMI CISPR22 Class A - CISPR22 Class A - CISPR22 Class A
*For 2000IRT2UXL—The product fulfils the requirement of IEC 62040-1: 2017+A1:2021, AS 62040.1:2019, EN IEC 62040-1:2019+A11:2021 and BS EN IEC
62040-1:2019+A11:2021.
Table 8.2 UPS Specifications, 1500 VA and 2000 VA Models (continued)
88 Proprietary and Confidential ©2024 Vertiv Group Corp. 8 Specifications
Vertiv™ Liebert® GXT5 UPS Installer/User Guide