Model GXT5 3000IRT2UXL 3000IRT2UXLA 3000IRT2UXLE
Rating 3000 VA/3000 W
Dimensions, D×W×H, in.(mm)
Unit 21.3 x 16.9 x 3.4 (540 × 430 × 85)
Shipping 28.2 x 22.4 x 10.3 (717 x 570 x 262)
Weight, lb.(Kg)
Unit 62 (28.2)
Shipping 79.2 (36) 72.6 (33)
Input AC
Voltage (typical) 230 VAC nominal; variable based on output load
90% to 100% loading 184 to 288 VAC
70% to 90% loading 161 to 288 VAC
50% to 70% loading 115 to 288 VAC
0 to50% loading 115 to 288 VAC
Frequency 40 Hz to 70 Hz; Auto Sensing
Input Power Cord C20
Output AC
Output Receptacles C13 x 6 and C19 x 1 C13 x 6 and C19 x 1 C13 x 6 and C19 x 1
Voltage 200/208/220/230/240 VAC (user-configurable); ±3%
Waveform Sine wave
Utility(AC) Model Overload >200% for 250 ms 150- 200% for 2 seconds 125- 150% for 50 seconds 105-125% 60 seconds
Internal Charger
Charging current Nominal 1.8 A; Maximum 8 A
Battery
Type Valve-regulated, non-spillable, lead acid
Qty×V×Rating 6 × 12V × 9.0 Ah
Backup time See Battery Run Times on page99.
Recharge Time 3 Hours to 90% capacity after full discharge with 100% load until UPS auto-shutdown (Internal Batteries Only)
Environmental Requirements
Operating Temperature, °F (°C) Operating temperature (full rating): 32 to 104 (0 to 40)
Extended Operating Temperature,
°F (°C)
32 to 122 (0 to 50); output derated by 1% per 1 °C above 40 °C
Storage Temperature, °F (°C) 5 to 122 (-15 to 50)
Table 8.3 UPS Specifications, 3000 VA Models
8 Specifications Proprietary and Confidential ©2024 Vertiv Group Corp. 89
Vertiv™ Liebert® GXT5 UPS Installer/User Guide

Table of Contents