Model GXT5 3000IRT2UXL 3000IRT2UXLA 3000IRT2UXLE
Rating 3000 VA/3000 W
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000 m) at 77 °F (25 °C) without derating
Audible Noise <48 dBA max at 3 ft. (1 m) front and sides <48 dBA max at 3 ft. (1 m) rear
Agency
Safety
EN 62040-1:2008+A1:2013; GS mark; UL
1778 5th Edition and CSA 22.2 No. 107.3
IEC 62040-1:2008+A1
EN 62040-1:2008+A1:2013; GS mark; UL
1778 5th Edition and CSA 22.2 No. 107.3
EMC
EN 62040-2:2006 EN 61000-3-2:2014 EN
61000-3-3:2013
-
EN 62040-2:2006 EN 61000-3-2:2014
EN 61000-3-3:2013
Transportation ISTA Procedure 1A - ISTA Procedure 1A
Surge Immunity ANSI C62.41 Category B IEC 61000-4-5 - ANSI C62.41 Category B IEC 61000-4-5
RFI/EMI CISPR22 Class A - CISPR22 Class A
*The product fulfils the requirement of IEC 62040-1: 2017+A1:2021, AS 62040.1:2019, EN IEC 62040-1:2019+A11:2021 and BS EN IEC 62040-
1:2019+A11:2021.
Table 8.3 UPS Specifications, 3000 VA Models (continued)
90 Proprietary and Confidential ©2024 Vertiv Group Corp. 8 Specifications
Vertiv™ Liebert® GXT5 UPS Installer/User Guide