Model GXT5 5000IRT5UXLN 5000IRT5UXLE 6000IRT5UXLN 6000IRT5UXLE
Rating 5000 VA/5000 W 6000 VA/6000 W
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x Voltage x Rating 16 x 12V x 9.0 AH
Back-up time See Table 8.16 on page102. See Table 8.17 on page103.
Upper-limit selections +10%, +15%, +20%; default +10%.
Lower-limit selections -10%, -15%, -20%; default -15%
Disable-bypass operation When the input frequency prevents synchronous operation.
Environmental Parameters
Operating Temperature, °F (°C) Operating temperature (full rating): 32 to 104 (0 to 40)
Extended Operating Temperature, °F (°C) 32 to 122 (0 to 50); output derated by 1% per 1 °C above 40 °C
Storage Temperature, °F (°C) 5 to 122 (-15 to 50)
Relative Humidity 0 – 95% non-condensing
Operating Elevation Up to 3,000 m (9,842.5 ft) at 25 °C (77 °F) without derating
Audible Noise <55 dBA, at 1 meter from the front, <50 dBA, at 1 meter from rear or sides
Agency Parameters
Safety IEC62040-1:2008 version, GS mark
EMI/EMC/C-Tick EMC IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6)
ESD IEC/EN EN61000-4-2, Level 4, Criteria A Radiated Susceptibility
Radiated Susceptibility IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient IEC/EN EN61000-4-4, Level 4, Criteria A
Surge Immunity IEC/EN EN61000-4-5, Level 4, Criteria A
Transportation ISTA Procedure 1E
Table 8.4 UPS Specifications, 5 kVA and 6 kVA Models (continued)
92 Proprietary and Confidential ©2024 Vertiv Group Corp. 8 Specifications
Vertiv™ Liebert® GXT5 UPS Installer/User Guide