Model GXT5 8000IRT5UXLN 8000IRT5UXLE 10KIRT5UXLN 10KIRT5UXLE
Rating 8000 VA/8000 W 10000 VA/10000 W
Dimensions, mm (in.)
Unit, WxDxH 430×630×217 (16.9×24.8×8.5)
Shipping, WxDxH 646×816×520 (25.4×32.1×20.5)
Weight, kg (lb)
Unit 74.5 (164.2)
Shipping 95 (209.4) 93 (205) 95 (209.4) 93 (205)
Input AC Parameters
Operating Frequency, Nom. 50 or 60 Hz (factory default is 50 Hz)
Factory default VAC 230 VAC
User configurable VAC 200/208/220/230/240 VAC (Adjustable using operation/display configuration options)
Operating voltage range without
battery operation
176 288 VAC (100 176 VAC with power derating)
Maximum Allowable VAC 288 VAC
Input frequency without battery
operation
40 70 Hz
Input Power Connection PD5-CE10HDWRMBS PD5-CE10HDWRMBS
Output AC Parameters
AC-AC Efficiency 94.5% 95%
Factory default VAC Frequency 230 VAC, 50 Hz
Output Power Connection PD5-CE10HDWRMBS PD5-CE10HDWRMBS
Waveform Sine wave
Main Mode Overload > 150% minimum 200 ms 125 150% for 60 seconds 105 125% for 5 minutes 105% continuous
Internal Battery Charger
Charger Current, A 1.8 A default, maximum 8 A
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x Voltage x Rating 16 x 12 V x 9.0 AH
Back-up time See Table 8.8 on page97.Table 8.18 on page103 See Table 8.9 on page98.
Upper-limit selections +10%, +15%, +20%; default +10%.
Lower-limit selections -10%, -15%, -20%; default -15%
Disable-bypass operation When the input frequency prevents synchronous operation.
Environmental Parameters
Table 8.5 UPS Specifications, 8 kVA and 10 kVA Models
8 Specifications Proprietary and Confidential ©2024 Vertiv Group Corp. 93