Web Server Settings
Web Server Protocol
Select the operation mode of the web server (HTTP, HTTPS).
HTTP Port
Standard web port not encrypted. Required if HTTP is enabled as web server protocol. Default is 80. Must be set to 80
for correct Vertiv™ Liebert® iCOM™ connection.
HTTPS Port
Standard secure web port; all communication is encrypted. Required if HTTPS is enabled as web server protocol.
Default is 443. Must be set to 443 for correct Liebert® iCOM™ connection.
Password Protected Site
When enabled, a log in session is required before any device information is displayed to the user. User level credentials
will allow only viewing of device information. Administrator level credentials are required to make any changes.
Default:enabled.
Remote Write Access
When enabled, all web browsers have write access to data on all Unity card web pages when the user is logged in with
Administrator credentials. When disabled, write access is restricted to web browsers connected on an
Autoconfiguration IPv4 address. An Autoconfiguration IPv4 address is of the form 169.254.x.x, and is negotiated
automatically when a direct connection is made between the Ethernet port of your PC and the Ethernet port of the
Unity card. Regardless of this setting, all web browsers always have read access to the web pages (subject to the
setting of the Password Protected Site parameter), and the diagnostic information file can be generated when the user
is logged in with Administrator credentials (see Unity Support Information on page151 ).
NOTE: When remote write access is disabled, an indicator is displayed in the upper right corner of the web page as a
reminder, shown in the following figure.
NOTE: Only disable remote write access if you are absolutely sure that you do not need to administer the managed
device or the Unity card through a remote web browser session.
Session Idle Timeout
The interval the software will wait before logging off a user unless there is user activity. The default is five minutes.
8 External Monitoring andBuilding ManagementSystems
130
Vertiv™ Liebert® iCOM™Installer/User Guide