NOTE: Depending on the type of thermal management unit, included components, and control settings of your system,
all of the options listed may not be available on your Vertiv™ Liebert® iCOM™ display.
9.4.2 Wired Remote Sensor Sensor Property Options
Function
Sets the function of the sensor when Unit Remote Sensors Mode is enabled.
• Disable: Sensor readings are ignored.
• Reference: Sensor readings are considered for Max Rack Temp, but are not used in maximum/average
calculations.
• Control: Sensor readings are used in maximum/average calculations.
Left Lead Current Value
Current reading of the left sensor probe. The left probe is always a temperature reading.
Left Lead Offset
Correction (calibration) value added to the reading. Used in the event that the sensor reading is incorrect.
• May be a positive or negative value.
Name
Custom, descriptive name to assist in identifying the sensor’s location/function in the facility, for example, the name of
the rack on which it is installed. The name is limited to:
• Up to 4 alphanumeric characters in length.
• Upper and lower case characters.
• These special characters: & * / . + - : @ \.
Right Lead Current Value
Current reading of the right sensor probe. May be a temperature or humidity reading, depending on the connected
sensor.
Right Lead Offset
Correction (calibration) value added to the reading. Used in the event that the sensor reading is incorrect.
• May be a positive or negative value.