Vertiv Liebert iCOM - 9.4.1 Wired Remote Sensor Setup Options

Vertiv Liebert iCOM
240 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NOTE: Depending on the type of thermal management unit, included components, and control settings of your system,
all of the options listed may not be available on your Vertiv™ Liebert® iCOM™ display.
9.4.2 Wired Remote Sensor Sensor Property Options
Function
Sets the function of the sensor when Unit Remote Sensors Mode is enabled.
Disable: Sensor readings are ignored.
Reference: Sensor readings are considered for Max Rack Temp, but are not used in maximum/average
calculations.
Control: Sensor readings are used in maximum/average calculations.
Left Lead Current Value
Current reading of the left sensor probe. The left probe is always a temperature reading.
Left Lead Offset
Correction (calibration) value added to the reading. Used in the event that the sensor reading is incorrect.
May be a positive or negative value.
Name
Custom, descriptive name to assist in identifying the sensor’s location/function in the facility, for example, the name of
the rack on which it is installed. The name is limited to:
Up to 4 alphanumeric characters in length.
Upper and lower case characters.
These special characters: & * / . + - : @ \.
Right Lead Current Value
Current reading of the right sensor probe. May be a temperature or humidity reading, depending on the connected
sensor.
Right Lead Offset
Correction (calibration) value added to the reading. Used in the event that the sensor reading is incorrect.
May be a positive or negative value.
9 Configuring Auxiliary Devices
159
Vertiv™ Liebert® iCOM™Installer/User Guide