4. Touch Name, and use the keyboard to give the sensor a descriptive name.
NOTE: This is the name displayed on the REMOTE SENSORS panel for non-service users.
5. Refer to the Wired Remote Sensor Sensor Property Options on the facing page to adjust the remaining settings,
and touch Save. The wired-remote sensors for the cooling unit are configured.
9.4.1 Wired Remote Sensor Setup Options
Average Rack Temp
Calculated average of temperature readings from the control sensors.
Individual Remote Sensors Mode
When controlling at the sensor level, selects the method of using the readings from the two temperature thermistors
(probes) on the sensor. Options are:
• Maximum: Use the highest temperature reading of the two thermistors.
• Average: Use the average of the readings from the two thermistors.
Max Rack Temp
Highest temperature reading from the unit remote sensors.
REM Sensors Set to Control
Number of sensors set to control.
Unit Remote Sensors Mode
When controlling at the unit level, selects the method of using the inlet rack temperature readings from the control
sensors to control fan speed. Options are:
• Maximum: Use the highest temperature reading of the sensors set to Control.
• Average: Use the average of the readings from the sensors set to Control and included in AVG.
Unit Remote Sensors Included in AVG
When Unit Remote Sensors Mode is Average, selects the number of sensors used to calculate the average
temperature.
• If the number selected is smaller than the number of REM Sensors set to Control, only the highest readings are
used for the calculation.