8.2.5 Local Users Configuration
Local Users offers up to 10 users and three access levels described in Table 8.2 below .
The default password for all users is Liebert (case sensitive).
Level Name
Access/
Permission
Type
Description
No Access None The No Access level is enforced when Password Protected Site is enabled.
General User Read-only
Able to view all tabs, folders and sub-folders of the user interface.
A General User will only need to enter the assigned password if Password Protected Site is enabled, see Web Server
Configuration on page129 .
Administrator Read/Write
Able to edit settings using the assigned password, which is always required to edit settings/configuration.
CWE-521: Minimum of 8 to a maximum of 30 case-sensitive, printable characters (excluding: \’<>~?#, double quote
and space). Also must contain a combination of upper and lower case, digit and special characters. The password
cannot contain the username.
Table 8.2 User Access Levels
IMPORTANT! Record user names and passwords and save them in a secure place where they can be found if
forgotten. A lost password cannot be retrieved from the IS-UNITY card. If the administrator password is lost, the card
must be reset to factory defaults and reconfigured.
To Change the User Names and Passwords
NOTE: CWE-521, Password Complexity requires the following:
Minimum of 8 to a maximum of 30 case-sensitive, printable characters (excluding: \’<>~?#, double quote and space).
Also must contain a combination of upper and lower case, digit and special characters. The password cannot contain
the username.
1. Touch , then > BMS & Teamwork > IS-Unity
Setup > Configuration > Users > User [n].
2. Enter a new user name and password.
3. Re-enter the password to confirm it.
4. In Authorization for User, select the type of access, see Table 8.2 above .
5. Touch Save.
8 External Monitoring andBuilding ManagementSystems
126
Vertiv™ Liebert® iCOM™Installer/User Guide