Setting Low Pressure Time Delay
At compressor start up, a low pressure condition is ignored for a set period to avoid false trips due to bubbles in the
refrigerant or other misreading of the low pressure device.
NOTE: The factory-default setting is a three minute delay for air cooled units and a zero to one minute delay for water
cooled units.
1. Touch , then > Options Setup > Compressor Settings.
2. Use the Winter Start Delay slider to select the number of minutes for the delay, and touch Save.
Adjusting Ball Valve Pressure Offset
NOTE: Only a properly trained and qualified technician should modify the motorized ball valve setting.
The number of times the valve opens and closes is adjusted based on added pressure offset.
1. Touch , then > Options Setup > Compressor Settings.
2. Use the Ball Valve Setpoint Offset slider to select amount of pressure added to open the valve wider, and touch
Save.
Compressor Sequencing for Balancing Run Times
Compressor sequencing, available in two compressor cooling units, allows assigning a lead compressor or allowing
automatically leading with the compressor with the lower run hours logged.
When Auto is selected, the following applies as Liebert® iCOM™ attempts to maintain equal run time of the compressors:
If only one compressor is available because of safety delays, it is given first priority to start/stop.
If both compressors are off, the compressor with fewer run-hours in the next to start.
If both compressors are operating, the compressor operating for the longest time since the last start is the first to
shut off.
NOTE: Automatic compressor sequencing will not power off a compressor if it is required to properly condition the
space.
To set-up compressor sequencing:
1. Touch , then > Options Setup > Compressor Settings.
2. Select the Compressor Sequence option to use, and touch Save.
3 Service Operation
59
Vertiv™ Liebert® iCOM™Installer/User Guide