Event Description
PB1 OUT TEMP SEN FAIL
Outlet refrigerant-temperature-sensor failure. Pump shut down.
Event is reset when condition clears.
PB1 CAN DISCONNECTED
Liebert® iCOM™ lost CAN communications with pump board. Pump shut down.
Event is reset when condition clears.
PB1 REMOTE SHUTDWN
Remote shut-down requested. Pump shut down.
Event is reset when condition clears.
PB1 STARTUP FAIL
Three pump start up attempts in a row have failed.
Event must be reset manually.
PB2 BOARD FAIL
An unrecoverable failure of the pump control board occurred. Pump shut down.
Reboot pump board to reset event.
PB2 CAVITATE
SHUTDOWN
Pump has cavitated and shut down.
Event is reset when Liebert® iCOM™ requests a new startup.
PB2 IN PRES SENS FAIL
Inlet refrigerant-pressure-sensor failure. Pump shut down.
Event is reset when condition clears.
PB2 IN TEMP SENS FAIL
Inlet refrigerant-temperature-sensor failure. Pump shut down.
Event is reset when condition clears.
PB2 INV DATA
SHUTDOWN
Invalid data detected and pump shut down.
Event is reset when Liebert® iCOM™ requests a new startup.
PB2 LO DIFF PRESSURE
Pump differential pressure fell below a lower threshold and pump shut down.
Event is reset when Liebert® iCOM™ requests a new startup.
PB2 LO OUTLET TEMP
Pump outlet-refrigerant-temperature fell below a lower threshold and pump shut down.
Event is reset when Liebert® iCOM™ requests a new startup.
PB2 OUT PRES SEN FAIL
Outlet refrigerant pressure-sensor failure. Pump shut down.
Event is reset when condition clears.
PB2 OUT TEMP SEN FAIL
Outlet refrigerant temperature sensor failure. Pump shut down.
Event is reset when condition clears.
PB2 CAN DISCONNECTED
Liebert® iCOM™ lost CAN communication with pump board. Pump shut down.
Event is reset when condition clears.
PB2 REMOTE SHUTDWN
Remote shut-down requested. Pump shut down.
Event is reset when condition clears.
PB2 STARTUP FAIL
Three pump start-up attempts in a row have failed.
Event must be reset manually.
PB1 COMMUNICATE FAIL
Ethernet communications failure. Pump not shut down.
Event is reset when condition clears.
USB communications failure. Pump not shut down.
Event is reset when condition clears.
Table 4.4 Events Specific to Liebert® EconoPhase (continued)
4 Managing Events: Alarms,WarningsandMessages
89
Vertiv™ Liebert® iCOM™Installer/User Guide