[2] --- (A) 80 : 75 : 5 (B) 80 : 75 : 5 (C) 80 : 75 : 5
[2.A] --- (1) 75 : 70 : 5 (2) 75 : 70 : 5 (3) 75 : 70 : 5 (4) 75 : 70 : 5 (5) 75 : 70 : 5 (6) 75 : 70 : 5
[2.B] --- (1) 75 : 70 : 5 (2) 75 : 70 : 5 (3) 75 : 70 : 5 (4) 75 : 70 : 5 (5) 75 : 70 : 5 (6) 75 : 70 : 5
[2.C] --- (1) 75 : 70 : 5 (2) 75 : 70 : 5 (3) 75 : 70 : 5 (4) 75 : 70 : 5 (5) 75 : 70 : 5 (6) 75 : 70 : 5
To configure the threshold value for branch Aof PDU2, enter the following command.
cli->current threshold 2.A 80:75:5
To view the current untilalarm for branch Bof PDU2, enter the following command:
cli->current untilalarm 2.B
[2] --- (B) 6.00 A
To view the current utilization for PDU2, enter the following command.
cli->current utilization 2
[2] --- (L1) 79.17% (L2) 79.1 % (L3) 75.00%
[2] --- (A) 77.77% (B) 68.42% (C) 77.77%
[2.A] --- (1) 85.71% (2) 85.71% (3) 68.00% (4) 71.50% (5) 71.50% (6) 85.71%
[2.B] --- (1) 85.71% (2) 85.71% (3) 85.71 % (4) 71.50% (5) 68.00% (6) 68.00%
[2.C] --- (1) 68.00% (2) 71.50% (3) 71.50 % (4) 71.50% (5) 85.71% (6) 85.71%
Vertiv | RPC2™ Communications Module Command Reference Guide | 12