890362_b•en•21.03.2011 We reserve the right to carry out improvements
27
6.1.1 Adjusting the wind
monitor
The following parameters can be set for the wind monitor:
Lim. = Wind speed limit (0-20 m/s)
Dely = On delay, wind (0-20 s)
DelyE = Off delay, wind (0-99 min)
Alloc = Wind sensor allocation (1, 2, 3, 4, 1-4)
Test = Wind test (on/off)
Keep the disp/prog button pressed for approx. 5 seconds.
Wind: 8m/s 8m/s 8m/s 8m/s
Time: 10:26:47 Wednesday, 20.11.2008
The selection menu is displayed:
Select the Wind RunT Timer Sun
settings: Rain Temp Product -->
Press the
button above the word Wind.
The Wind menu is displayed:
Wind Lim. Dely Dely Alloc
settings: Test
Select the desired parameter by pressing the
or
button.
Example Wind speed limit (Lim.)
In this menu, you can change the settings for each facade (F1 - F4) using the
/
buttons.
Wind limit UP
: OFF OFF 12m/s 8m/s
CH1 CH2 CH3 CH4
Leave the menu after completing the entries using the disp/prog button.
This saves the changes you made.
Safety functions
Wind monitor