Operating instructions
7.3.4 Outside settings up/down,
inside settings up/down
The effects of the settings are addressed below in more detail.
A temperature control command can have a variety of effects, which you can
select in the Temp menu.
Limit values:
Normally, the DOWN limit value (Out
or In
) must be larger than the UP
limit value (Out
or In
): If the temperature reading exceeds the DOWN limit
value, the DOWN move command is triggered or the sun control is switched
on.
If the temperature reading drops below the UP limit value, an UP move com-
mand is triggered or the sun control is switched off and an UP move com-
mand is triggered.
NOTE The temperature control has no delays since temperatures change slowly.
7.3.5 InOM, OutOM, Alloc
settings
Operating modes:
If the inside/outside temperature control is to execute a move command, se-
lect the Move setting in the InOM, OutOM menus.
If the inside/outside temperature control is to enable the sun control, select
the Sun setting in the InOM, OutOM menus.
Allocation:
One outside temperature sensor and/or up to 4 inside temperature sensors
can be connected to the Quatronic dialog. These sensors are allocated to
the 4 facades in the Alloc menu.
Comfort functions
Temperature control