EasyManua.ls Logo

Weidmüller 610 - Commissioning (Continued); Deactivate Energy Meters; Tariffs via Profibus; Reading Out Measurement Values via the Profibus

Weidmüller 610
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
392576780000/00/02-2018
Commissioning
Deactivate energy meters / tariffs via Probus
If energy meters are assigned to a tariff then these can be deacti-
vated via byte 3 and byte 4 (cf. activate tariffs via Probus). Here
the selection of the desired tariff is implemented in byte 3 and the
clearing of the associated bits in byte 4 deactivates the energy
meter.
Example:
If the energy meter for active energy (drawn) is set under tariff 3,
the deactivation of the energy meter is implemented as follows:
Unused
Tariff 7 (0=inactive, 1=active)
Tariff 6 (0=inactive, 1=active)
Tariff 5 (0=inactive, 1=active)
Tariff 4 (0=inactive, 1=active)
Tariff 3 (0=inactive, 1=active)
Tariff 2 (0=inactive, 1=active)
Tariff 1 (0=inactive, 1=active)
Bit:
0
7 6
0
0
5
0
0
4
0
0
3
0
1
2
0
0
1
0
0
0
0
Fig.: Byte 3: Tariff 3 selected
Unused
Energy meter for apparent energy
Energy meter for reactive energy (cap.)
Energy meter for reactive energy (ind.)
Energy meter for reactive energy
Energy meter for active energy (delivered)
Energy meter for active energy (drawn)
Energy meter for active energy (without backstop)
Bit:
0
7 6
0
0
5
0
0
4
0
0
3
0
0
2
0
0
1
0
0
0
0
Fig.: Byte 4: Deactivating energy meters
The energy meter is deleted by selecting the tariff (byte 3) and
clearing the bits in byte 4 associated with the energy meter.
If the meter is deleted then a new energy meter can be assigned
to the tariff.
If the deactivation of a tariff is desired then the energy meters
assigned should be deleted rst via bytes 3 and 4 and then
the tariff should be deactivated via byte 3.
Reading out measurement values via the Probus
Selected measurement values can be read out via 4 factory-set
proles and an additional 8 user-dened proles. Here each prole
has a unique prole number with which a PLC can read out the
congured measurement values of a prole.
Example:
Reading out of measurement values from the factory-precong-
ured Probus prole number 8.
The 1st byte should be set to the prole number 8 (dec.) and sent
to the Energy Meter 610-PB.
The Energy Meter 610-PB then delivers the prole number 8 and
the measured values set in prole 8 back.
Bit:
0
7 6
0
5
0
4
0
1
3
0
0
2
0
0
1
0
0
0
Fig.: Byte 1: Prole number 8 selection
The device address can be congured by using the pa-
rameter 000 if the device is used in a Probus-System.
The baud rate in a Probus system is detected auto-
matically and must NOT be set via the address 001!

Table of Contents

Related product manuals