EasyManuals Logo

Xantrex XW User Manual

Xantrex XW
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
Installing the XW Automatic Generator Start
975-0307-01-01 2–5
Wiring to the 20-contact Connector
ELV Circuits ELV (Extra-Low Voltage) circuits have an open-circuit voltage of not
more than 30 V
rms
or 42.2 VDC or peak, and are therefore not a shock
hazard.
Class 2 Circuits As per the US National Electrical Code (NEC) and the Canadian
Electrical Code (CEC), available power in Class 2 circuits is limited to
100 VA, usually by current limiting by means of overcurrent protection or
series resistance. The current is limited to 5 A for circuits with open-
circuit voltage of 20 V, and to I=100/V
oc
for circuits with open circuit
voltage between 20 V and 30 V.
Circuit
Limitations
The relay contacts in the XW Auto Generator Start are rated at 5 A
maximum and all circuits on the 20-contact connector are rated at 30 V
maximum.
Ensure that all circuits connected to the 20-contact connector comply with
the following limits:
Wiring Harness Connections to the generator, thermostats, and external ON/OFF switches
are made using a wiring harness that plugs into the 20-contact connector
(see Figure 2-1).
CAUTION: Shock Hazard
All installation wiring should be performed by a qualified installer or electrician.
WARNING: Fire, Shock, and Energy Hazards
The 20-contact connector is intended for connection to Class 2 ELV (Extra Low
Voltage) circuits only. Do not exceed the circuit limitations specified in the
following section.
Table 2-1
Circuit Limitations
Circuit Parameter Circuit Maximum
Open circuit voltage (Voc) 30 V maximum
Overcurrent protection
(fuse size for open circuit voltage up to 20 V)
5 A maximum
Overcurrent protection
(fuse size for open circuit voltage from 20 V to 30 V)
5 A to 3.33 A
(100/V
oc
amps
maximum)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xantrex XW and is the answer not in the manual?

Xantrex XW Specifications

General IconGeneral
Maximum Power Point Tracking (MPPT)Yes
ModelXW
CategoryController
Maximum PV Array Voltage150V
Nominal Battery Voltage48V
Output Voltage48V

Related product manuals