Troubleshooting
5–6 975-0307-01-01
Fault Messages
When the XW Auto Generator Start detects a fault condition, it stops the
generator. The red Fault light also comes on, and the XW System Control
Panel displays a fault message.
The XW Auto Generator Start remembers the GenMode that it was in at
the time it detected the fault. After you have cleared the fault, the XW
Auto Generator Start returns to its last known GenMode.
Table 5-2
XW Auto Generator Start Fault Messages
Fault
Number Message
Self-
clearing? Cause Action
F200 Exceeded max
number of start
tries. Check gen,
clear fault.
No The XW Auto Generator Start
has tried and failed to start the
generator. To prevent draining
the start battery, the XW Auto
Generator Start will suspend
further start attempts.
Check the generators fuel
level and start battery
condition. Consult
generator manual.
Clear fault on System
Control Panel screen to
allow retry.
F201 Unable to stop
gen. Stop gen via
its control panel.
No The XW Auto Generator Start
has lost contact with the
generator or the generator did
not stop after the XW Auto
Generator Start sent it a stop
signal.
Change the XW Auto
Generator Start mode to
Manual Off.
If this fails to work, stop
the generator with the
external stop switch.
Check generator.
Return XW Auto
Generator Start to
automatic mode to resume
automatic starts and stops.
F203 Manual Off: Gen
stopped by ext
sensor. Reset
GenMode.
No An external sensor connected
to the XW Auto Generator
Start has stopped the generator
and put the XW Auto
Generator Start into Manual
Off mode.
After the sensor
connected to the external
shutdown has deactivated,
clear the fault and reset
the XW Auto Generator
Start to the desired mode.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xantrex XW and is the answer not in the manual?

Xantrex XW Specifications

General IconGeneral
Maximum Power Point Tracking (MPPT)Yes
ModelXW
CategoryController
Maximum PV Array Voltage150V
Nominal Battery Voltage48V
Output Voltage48V

Related product manuals