Warning Messages
975-0307-01-01 5–5
W250 The selected value
failed to change.
Try again.
No You have tried to change
the Gen Type without
putting the system into
Standby first.
Put the system into
Standby, change the Gen
Type, then return the
system to Operating mode.
You have tried to set the
“Exercise Dur” for longer
than “Max Run Time,” or
“Max Run Time” for less
than “Exercise Dur.”
Ensure that “Max Run
Time” is set for longer than
“Exercise Dur.”
W500 Network
connection lost.
Check connections.
Yes The XW Auto Generator
Start has lost
communications with the
network because of a faulty
connection or electronic
signal disruption.
Check connection between
the XW Auto Generator
Start and the network.
W501 XW Auto
Generator Start has
fixed memory
problem and
restored default
settings.
No The XW Auto Generator
Start encountered an
internal memory problem
upon startup. To remain
operational, the XW Auto
Generator Start restored its
default settings.
Acknowledge the warning
and reset configurable
settings if necessary.
Table 5-1
XW Auto Generator Start Warning Messages(Continued)