The XW Auto Gen Start Menu
975-0307-01-01 3–7
The Configuration Menu
The Configuration Menu is where specific start-stop parameters are set.
This menu contains the following settings:
QT EN
•QT Begin
QT END
•Gen Type
•Cfg Trigger
•Cfg Gen
Multi-unit Config
Restore Defaults
QT En
Full name Quiet Time Enable
Purpose “QT En” enables or disables the Quiet Time functionality of the XW Auto
Generator Start. Quiet time refers to a period of time when the generator
should not run.
Dependencies “QT En” requires the XW Auto Generator Start to be in Automatic mode.
Setting “QT En” to [Enable] requires that parameters be set for the “QT
Begin” and “QT End”.
When to use Set “QT En” to [Enabled] when there is a period of time when it is not
desired for the generator to run. The XW Auto Generator Start will ignore
all automatic start triggers during the time set in “QT Begin” and “QT
Begin”.
When there are no preferences or restrictions for when the generator
should run, set “QT En” to [
Disabled]. When [Disabled] is selected, the
XW Auto Generator Start will ignore the times set for “QT Begin” and
“QT End”.
Considerations Quiet Time prevents the automatic starting of the generator regardless of
battery condition.
Value Description
Enabled/Disabled Enables or disables the Quiet Time functionality.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xantrex XW and is the answer not in the manual?

Xantrex XW Specifications

General IconGeneral
Maximum Power Point Tracking (MPPT)Yes
ModelXW
CategoryController
Maximum PV Array Voltage150V
Nominal Battery Voltage48V
Output Voltage48V