2.2 A: Initialization Parameters
154 YASKAWA TOEPYAIGA5002A GA500 Programming
Figure 2.6 DC Injection Braking at Stop Function
Note:
If the mechanical operation of the holding brake is slow, use DC Injection Braking until the brake is fully closed to prevent rollback.
If you cannot hold the load with DC Injection Braking when it is stopped in V/f Control and Open Loop Vector Control modes, use Dwell
Function at Stop.
b6-03 [Dwell Reference at Stop]: Minimum output frequency to 3.0 Hz
When Frequency Detection 2 is OFF, it is less than L4-01 [Speed Agree Detection Level] - L4-02 [Speed Agree Detection Width].
b6-04 [Dwell Time at Stop] recommended setting: 0.3 s to 0.5 s
b2-04 [DC Inject Braking Time at Stop] recommended setting: 0.0 s
Torque Compensation (Torque Bias)
You must detect the load and motoring/regeneration on the machine side before you use the function. If there is a
polarity error, shock can increase.