EasyManua.ls Logo

YASKAWA GA500 series - Page 166

YASKAWA GA500 series
526 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.3 b: Application
166 YASKAWA TOEPYAIGA5002A GA500 Programming
Figure 2.16 Example of Setting the Frequency Reference with a Voltage Signal to Terminal A1
Note:
You can also use this diagram to wire terminal A2.
Current Input
Refer to Table 2.22 to use a current signal input to one of the MFAI terminals.
Table 2.22 Frequency Reference Current Input
Terminal Signal Level
Parameter Settings
Note
Signal Level
Selection
Function Selection Gain Bias
A2 4 - 20 mA H3-09 = 2 H3-10 = 0
[Frequency Reference]
H3-11 H3-12 Set DIP switch S1 to I
for current input.
0 - 20 mA H3-09 = 3
Figure 2.17 Example of Setting the Frequency Reference with a Current Signal to Terminal A2
Changing between Master and Auxiliary Frequency References
Use the multi-step speed reference function to change the frequency reference input between terminals A1 and A2.
2 : Memobus/Modbus Communications
Use MEMOBUS/Modbus communications to enter the frequency reference.
3 : Option PCB
Use a communications option card connected to the drive to enter the Run command.
Refer to the instruction manual included with the option card to install and set the option card.
Note:
If you set b1-15 = 3 but you do not connect an option card, oPE03 [Multi-Function Input Setting Err] will flash on the keypad.
4 : Pulse Train Input

Table of Contents

Other manuals for YASKAWA GA500 series

Related product manuals