Parameter Details
2
2.8 H: Terminal Function Selection
YASKAWA TOEPYAIGA5002A GA500 Programming 321
ON : The output frequency is higher than the value of L4-01.
OFF : The output frequency is less than the value of L4-01 - L4-02,” or it is not more than the value
of L4-01.
Figure 2.78 Frequency Detection 2 Time Chart
6: Drive Ready
Setting Value Function Description
6 Drive ready
The terminal activates when the drive is ready and running.
The terminal deactivates in these conditions:
When the power supply is OFF
During a fault
When there is problem with the control power supply
When there is a parameter setting error and the drive cannot operate although there is a Run command
When you enter a Run command and it immediately triggers an overvoltage or undervoltage fault because the drive
has an overvoltage or undervoltage fault during stop
When the drive is in Programming Mode and will not accept a Run command
When the Safe Disable function is active
7: DC Bus Undervoltage
Setting Value Function Description
7 DC Bus Undervoltage
The terminal activates when the DC bus voltage or control circuit power supply is less than the voltage set with L2-05
[Undervoltage Detection Lvl (Uv1)]. The terminal also turns on when there is a fault with the DC bus voltage.
ON : The DC bus voltage is less than the setting value of L2-05.
OFF : The DC bus voltage is more than the setting value of L2-05.
8: During Baseblock (N.O.)
Setting Value Function Description
8 During Baseblock (N.O.)
The terminal turns on during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not
make DC bus voltage.
ON : During baseblock
OFF : The drive is not in baseblock.
9: Frequency Reference from Keypad
Setting Value Function Description
9 Frequency Reference from
Keypad
Shows the selected frequency reference source.
ON : The keypad is the frequency reference source.
OFF : b1-01 or b1-15 [Frequency Reference Selection 1 or 2] is the frequency reference source.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV