2.8 H: Terminal Function Selection
322 YASKAWA TOEPYAIGA5002A GA500 Programming
■ A: Run Command from Keypad
Setting Value Function Description
A Run Command Source
Shows the selected Run command source.
ON : The keypad is the Run command source.
OFF : b1-02 or b1-16 [Run Command Selection 1 or 2] is the Run command source.
■ B: Torque Detection 1 (N.O.)
Setting Value Function Description
B Torque Detection 1 (N.O.)
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque is more than L6-02 [Torque Detection Level 1], or the level is less
than L6-02 for longer than L6-03 [Torque Detection Time 1].
Note:
• When L6-01 ≥ 5, the drive will detect when the output current/torque is less than L6-02 for longer than L6-03.
• Refer to L6: Torque Detection on page 389 for more information.
■ C: Frequency Reference Loss
Setting Value Function Description
C Frequency Reference Loss
The terminal activates when the drive detects a loss of frequency reference.
Note:
Refer to “L4-05: Fref Loss Detection Selection” for more information.
■ D: Braking Resistor Fault
Setting Value Function Description
D Braking Resistor Fault
The terminal activates when the mounting-type braking resistor is overheating or when there is a braking transistor fault.
■ E: Fault
Setting Value Function Description
E Fault
The terminal activates when the drive detects a fault.
Note:
The terminal will not activate for CPF00 and CPF01 [Control Circuit Error] faults.
■ F: Not Used
Setting Value Function Description
F Not Used
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact output via
MEMOBUS/Modbus or the communication option. This signal does not function if signals from the PLC are not configured.
■ 10: Alarm
Setting Value Function Description
10 Alarm
The terminal turns on when the drive detects a minor fault.