1.10 H: Terminal Functions
58 YASKAWA TOEPYAIGA5002A GA500 Programming
Setting Value Function Description Ref.
13 Speed Agree 2
The terminal activates when the output frequency is in the range of the frequency reference ± L4-04 [Speed Agree
Detection Width(+/-)].
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency is in the range of frequency reference ± L4-04.
OFF : The output frequency is not in the range of frequency reference ± L4-04.
323
14 User-Set Speed Agree 2
The terminal activates when the output frequency is in the range of L4-03 [Speed Agree Detection Level(+/-)] ± L4-04
[Speed Agree Detection Width(+/-)] and in the range of the frequency reference ± L4-04.
Note:
The detection level set with L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency is in the range of L4-03 ± L4-04 and the range of frequency reference ± L4-04.
OFF : The output frequency is not in the range of L4-03 ± L4-04 nor the range of frequency reference ± L4-04.
323
15 Frequency Detection 3
The terminal deactivates when the output frequency is higher than the value of L4-03 [Speed Agree Detection Level
(+/-)] + L4-04 [Speed Agree Detection Width(+/-)]. After the terminal deactivates, the terminal stays deactivated until
the output frequency is at the value of L4-03.
Note:
The detection level set with L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency is less than the value of L4-03 or does not exceed the value of L4-03 + L4-04.
OFF : The output frequency is higher than the value of L4-03 + L4-04.
324
16 Frequency Detection 4
The terminal activates when the output frequency is higher than the value of L4-03 [Speed Agree Detection Level
(+/-)]. After the terminal activates, the terminal stays activated until the output frequency is at the value of L4-03 - L4-
04.
Note:
The detection level set with L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency is higher than the value of L4-03.
OFF : The output frequency is less than the value of L4-03 - L4-04, or it does not exceed the value of L4-03.
324
17 Torque Detection 1 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque is more than the torque value set with L6-02 [Torque Detection Level 1], or the level
is less than the torque value set with L6-02 [Torque Detection Level 1] for longer than the time set with L6-03 [Torque
Detection Time 1].
325
18 Torque Detection 2 (N.
O.)
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque is more than the torque value set with L6-05 [Torque Detection Level 2], or the level is
less than the torque value set with L6-05 [Torque Detection Level 2] for longer than the time set with L6-06 [Torque
Detection Time 2].
325
19 Torque Detection 2 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque is more than the torque value set with L6-05 [Torque Detection Level 2], or the level
is less than the torque value set with L6-05 [Torque Detection Level 2] for longer than the time set with L6-06 [Torque
Detection Time 2].
325
1A During reverse
The terminal activates when the motor operates in the reverse direction.
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
325
1B During Baseblock (N.C.)
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching
and does not make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
326
1C Motor 2 Selected
The terminal activates when motor 2 is selected.
ON : Motor 2 Selection
OFF : Motor 1 Selection
326
1E Executing Auto-Restart
The terminal activates when the Auto Restart function is trying to restart after a fault.
326
1F Motor Overload Alarm
(oL1)
The terminal activates when the electronic thermal protection value of the motor overload protective function is a
minimum of 90% of the detection level.
326
20 Drive Overheat Pre-
Alarm (oH)
The terminal activates when the drive heatsink temperature is at the level set with L8-02 [Overheat Alarm Level].
326
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV