5-54
Continued
C. n074 : Stall Prevention Level At Set Speed Factory setting: See Table A3-1
(StallP Run Lvl)
Range: 30 - 200 %
This parameter determines the
actual drive output current level
while operating at set speed
(frequency). Set in percent of
drive rated output current (see
Appendix 2).
A setting of " 200 " disables stall
prevention at set speed. During
running at set speed, if the
output current exceeds the value
set in n074 , the drive will begin
to decelerate. When the output
current goes below the value set
in n074, acceleration begins, up
to the set frequency.
5.24 STALL PREVENTION