SECTION C. ALL GPD 506s (CONTINUED)
Location Indoor (protected from corrosive gases and dust).
Ambient Temperature –10 to 40°C (+14 to 104°F) for NEMA 1;
–10 to 45°C (+14 to 113°F) for protected chassis
Environmental
Conditions Storage Temperature (Note 3) –20 to 60°C (–4 to 140°F)
Humidity 95% RH (no condensation)
Vibration 1 G at less than 20 Hz, up to 0.2 G at 20 to 50 Hz.
SECTION B. ALL GPD 506/P5s (Continued)
NOTES:
1. Overload capacity: 120% of rated for 60 sec.
2. See paragraph 5.17 for detailed information.
3. Temperature during shipping. Storing in this temperature for a long period may deteriorate main circuit capacitor.
Table A2-1. Standard Specifications (Continued)
A2-4