SECTION A. 230V
TERMINAL FUNCTION
P 3 TO 40 HP
L1 (R)
Three phase Main circuit input power supply
L2 (S)
200 / 208 / 220V at 50 Hz; 200 / 208 / 220 / 230V at 60 Hz
L3 (T)
L11 Three phase Main circuit
L21 – – – – – – input power supply
L31 (same as at L1, L2 & L3)
T1 (U)
Three phase AC output to motor
T2 (V)
0V to max. input voltage level
T3 (W)
B1
B2
DB Unit terminals (B1 & B2) – – – – – –
-
1
DC Reactor terminals ( 1 & 2)
– – – – – –
2
DC Bus terminals ( 1 &
-
)
3 – – – – – – DB Unit terminals ( 3 &
-
) – – – – – –
Ground terminal (100 ohms or less)
0 HPF
L1 (R)
Three phase Main circuit input power supply
L2 (S)
380 / 400 / 415 / 460V at 50/60 Hz
L3 (T)
L11 Three phase Main circuit
L21 – – – – – – input power supply – – – – – –
L31 (same as at L1, L2 & L3)
T1 (U)
Three phase AC output to motor
T2 (V)
0V to max. input voltage level
T3 (W)
B1
B2
DB Unit terminals (B1 & B2) – – – – – –
-
1
DC Reactor terminals ( 1 & 2)
– – – – – –
2
DC Bus terminals ( 1 &
-
)
3 – – – – – – DB Unit terminals ( 3 &
-
)
l
1
(r) Power for heat sink fan:
l
2
200 (
s
200) – – – – – –
l
1
to
l
2
200: 230 Vac
l
2 400 (
s
400)
l
1 to
l
2 400: 460 Vac
Ground terminal (10 ohms or less)
1-6
SECTION A. 230V
FUNCTION
TERMINAL
SECTION B. 460V
FUNCTION
TERMINAL
Table 1-2. Typical Terminal Functions and Voltages of Main Circuit
– – – – – indicates that terminals are not present.
20P41F - 27P51F
A003-A036
20111F - 20151F
A054 - A068
20181F - 20750F
A080 - A312
40P41F - 40151F
B001 - B034
40181F - 41600F
B041 - B302
41850F - 43000F
B380 - B675
New Drive Model No.
CIMR-P5
Old Drive Model No.
GPD506V
New Drive Model No.
CIMR-P5
Old Drive Model No.
GPD506V

Table of Contents