In order to conform to EMC standards, the exclusive-use methods are required for line filter
application, cable shielding and drive installation. The following explains the outline of the
methods.
The line filter and drive must be mounted on the same metal plate. The filter should be
mounted as close to the drive as practical. Keep cable as short as possible. The metal
plate should be securely grounded. The ground of line filter and drive must be bonded to
the metal plate with as much area as possible.
For mains input cables, screened cable is recommended at least within the panel. The
screen of the cable should be connected to solid ground. For motor cable, screened cable
(max. 20 m) must be used and the screen of the motor cable should be connected to
ground at both ends by a short connection, using as large an area as practical.
For more detailed explanation, refer to Yaskawa document TD 4077, “Installation Guidelines
For EMC Directive using Yaskawa AC Drive Products.”
Table 1-4 and Figure 1-2A show the line filter list for EMC standards and the
installation/wiring of drive and line filter.
TTaabbllee 11--44.. LLiinnee FFiilltteerrss ffoorr GGPPDD 550066//PP55
1-14
New Old
Drive Model Drive Model
Line Filter
Number Number Part Number Rated Mass Dimensions in mm
(1)
CIMR-P5M GPD506V- 05P00325- Current (A) (kg) L x W x D
(2)
40P41F B001
40P71F B003
0106 8 1.8 320 x 143 x 46
41P51F B004
43P71F B008 0103 20 1.8 320 x 143 x 46
44P01F B011
45P51F B014
0104 30 3.0 350 x 213 x 51
47P51F B021
40111F B027
0105 60 5.3 435 x 268 x 56
40151F B034
40181F B041
0107 80 7.5 350 x 180 x 90
40221F B052
40301F B065 0108 100 13.8 420 x 200 x 130
40371F B080 0109 150 13.8 480 x 200 x 160
40451F B096 0110 160 25 480 x 200 x 160
40551F B128 0111 180 25 480 x 200 x 160
40750F B180
0112 300 25 480 x 200 x 160
41100F B240
41600F B302 0113 400 45 588 x 250 x 200
41850F B380 0119 500
42200F B506 0120 600
43000F B675 0121 900
(1) 1mm =
0.0394 inches
(2)
D is the distance the filter will extend outward from the surface of the metal plate.