5-42
Continued
n075 : Speed Coincidence Frequency / Frequency Factory setting: 0.0 Hz
Detection Level
Range: 0.0 to 400.0 Hz
(Freq Det Level)
Speed coincidence is used to control an output contact at terminals MA or MB (with
respect to terminal MC), or terminals M1 & M2, when selected by n041 and n042.
n041 or n042 : Multi-Fuction Output Terminals
(Terminal MA Sel) or (Terminal M1 Sel)
The output contact will close, dependent upon the data programmed into n041 or no42 .
See the appropriate figure below for operation.
A. Speed at Set Frequency B. Speed Coincidence
(setting: n041 or n042 = (setting: n041 or n042 =
"At Speed" (" 2 ")) "At Desired Speed" (" 3 "))
C. Frequency Detection – Low D. Frequency Detection – High
(setting: n041 or n042 = (setting: n041 or n042 =
"Freq Detection 1) (" 4 ")) "Freq Detection 2) (" 5 "))
n076 : Frequency Agreed Detection Width Factory Setting: 2.0Hz
(Freq Det Width) Range: 0.0 to 25.50 Hz
This Detection Width setting is used to establish the frequency level at which the output
contact activates, when n041 or n042 is set to "At Speed" (" 2 ") or "At Desired
Speed" (" 3 ").
5.20 MULTI-FUNCTION OUTPUT TERMINALS