Continued
n108 : Motor No-Load Current Factory setting: 2.0 sec.
(Mtr No-Load Amp)
Range: 0.0 to 25.5 sec.
Motor no-load current (n108 ) is set as a percentage of motor full-load current (n033 ). It
is used as shown in the slip compensation block diagram. The factory setting of 30% should
be sufficient for most motors.
n109 : Slip Compensation Primary Delay Factory setting: 2.0 sec.
Time Constant
Range: 0.0 to 25.5 sec.
( Slip Comp Delay)
Parameter (n109 ) can be increased to improve stability or decreased to improve response
to load changes.