Configuring Each Function
3-25
HW1484764
3.6. Configuring the Force Detection Hold Function
(Supported Only by YRC1000 System Version YAS2.41 or Later and
YRC1000micro System Version YBS2.10 or Later)
You can change the operation thresholds of the force detection hold function by setting the
following D variables to a percentage of the start threshold for the avoidance function. Setting the
thresholds to zero (0) disables the force detection hold function.
The thresholds are set to zero (0) by factory default.
The force detection hold function uses the threshold for your selected avoidance mode if the
avoidance function is enabled or the thresholds for both joint and translation modes if the
avoidance function is disabled.
In translation mode, the force acting on the TCP in the cartesian coordinate system is compared
with the thresholds.
Variable
Description
Unit
D397
Threshold addition percentage in joint mode
%
D398
Threshold addition percentage in translation mode
%
Use the following formula:
Force detection hold threshold = avoidance operation start threshold x (100 + threshold addition
percentage)/100
Refer also to the variables list in Chapter 8.
48/105