7. Alarm List
7.1. Major Alarms
Verify error
(system
configuration data)
(1) Verify the following settings.
- In the maintenance mode, select {FILE} -
{INITIALIZE}, and then execute "PFL Board FLASH
Reset".
(2) Turn off and on the power.
(1) Turn off and on the power.
(2) If the alarm recurs, replace the AIF01 board.
Save CMOS.BIN before replacing the board.
After replacing the AIF01 board, load CMOS.BIN saved
before the occurrence of the alarm.
(1) Turn off and on the power.
(2) If the alarm recurs, replace the ASF04 board.
Save CMOS.BIN before replacing the board.
If the alarm recurs after you have taken the action
described above, save CMOS.BIN and send the
description of when and how the alarm occurred
(operating steps, etc.) to Yaskawa representative.
(1) Turn off and on the power.
(2) If the alarm recurs, check if the following cables and
connectors are properly connected or inserted.
- ASF04 board CN235, CN236, CN237, CN238
(1) Turn off and on the power.
(2) If the alarm recurs, replace the ASF04 board.
If the alarm recurs after you have taken the action
described above, save CMOS.BIN and send the
description of when and how the alarm occurred
(operating steps, etc.) to your YASKAWA
representative.