Configuring Each Function
3-2
HW1484764
3.2. Basic Settings for Collaborative Operation
3.2.1. Changing the External Force Limits
To change the external force limits PFL function monitors, use the following steps
(1) Select {SAFETY FUNC.} - {EXTERNAL FORCE LIMIT SETTING} under the main menu.
(2) Select the file number for the external force limit you want to configure. To configure more than
one external force limit, you must configure as many limit files as the limits. You can configure and
save up to 32 limit files.
CAUTION
You are recommended not to enable more than five limit files at a time. You can enable six or
more limit files but doing so may result in a longer time taken to judge the external forces.
Disabling all the external force limit files disables the PFL function itself.
NOTICE
By factory default, the file number 1 is enabled and the external force limit for the TCP resultant
force and the external forces along the X-, Y-, and Z-axes is set to 100 N.