June. 14, 2017-00
FAILOUTPUT(/FL)
• Contact:Ccontact,1point
• FAILoutput:
The relay contact output on the rear panel
indicatestheoccurrenceofCPUfailure.
Relayoperation:Energizedduringnormal
operationandde-energizedonCPUfailure.
• Statusoutput:Therelaycontact,whichisde-
energizedinnormaloutputstate,isenergized
upontheoccurrenceofamemory/mediaerror,
measurementerror,communicationerror,
recordingstop,oralarm.
• Ratedpowersupplyvoltage:24VDCor250V
AC or less
• Ratedloadcurrent:3A(DC)/3A(AC),resistance
load
• Min.loadcurrent:100mA
• Recommendedreplacementperiodsofcontact:
Electrical:30,000moreON-OFFoperations,
Mechanical:5,000,000moreON-OFFoperations
LogSCALE(/LG)
Alogarithmicvoltagethathasbeenconvertedfrom
aphysicalvalueisappliedtotheGP,andthenthe
GP’sLogscale(logarithmicscale)isusedtodisplay
andrecordthephysicalvalue.
• Inputtype:Loginput(logarithmicinput),Pseudo
log input: An input that supports pseudo
logs,Loglinearinput:Inputthatislinearona
logarithmicscale.
• Range:20mV/60mV/200mV/1V/2V/6V/20V/50V/
100V
• Scalablerange:
• Loginput:
1.00E-15to1.00E+15(15decade
maximum)
Scale_L<Scale_U
Ifthelowerlimitmantissais1.00,the
differencebetweentheexponentsmustbe
1ormore.
Ifthelowerlimitmantissaisavalueother
than1.00,thedifferencebetweenthe
exponentsmustbe2ormore.
• PseudoLogInput/Loglinearinput
1.00E-15to1.00E+15(15decade
maximum)
Thehigherlimitmantissaisthesameas
thelowerlimitmantissa).
Ifthelowerlimitmantissais1.00,thevalue
mustbebetween1.00E–15and1.00E+15,
thedifferencebetweentheexponentsmust
be1ormore,andthemaximumdecadesis
15.
Ifthelowerlimitmantissaisavalueother
than1.00,thevaluemustbebetween
1.01E–15and9.99E+14,thedifference
betweentheexponentsmustbe1ormore
andthemaximumdecadesis15.
• Alarmtype:Highlimit,lowlimit,delayhighlimit,
anddelaylowlimit
• Alarmsettingrange:Therangeconvertedinto
theLOGscalecorrespondingto-5%to105%of
the span width.
• Alarmhysteresis:Fixedto0
• Greenbandsettingrange:Thelowerlimittothe
upperlimitofthescale.However,thelowerlimit
ofthedisplaypositionmustbesmallerthanthe
upperlimit.
• Positionofthedecimalpoint:1to2
• Misc:Nonlinearinputispossiblebycorrecting
theinputvalue
MATHEMATICAL FUNCTIONS WITH REPORT
FUNCTION(/MT)
MathematicalFunction:
• Numberofmathchannels;GP10:50,GP20-1:
100, GP20-2: 200
Note) Note:Dependingonthemeasurementmode,
thereisalimittothenumberofmathchannels
atscanintervalsshorterthan100ms.See
“Limitations.”
• Scaninterval
Measurementmode Scaninterval
Normal Scaninterval
High speed Scaninterval
Dualinterval Masterscaninterval*
* WhenthemeasurementmodeisDualinterval,
thisitemsetswhichscanintervaltouse,the
intervalofmeasurementgroup1orthatofscan
group2,forcreatingmeasuredvaluesofmath
orcommunicationchannelsandothersimilar
operations.
• Numberofexpressions:
• Operation:
Generalarithmeticoperations:Fourarithmetic
operations(+,-,*,/),squareroot,absolute,
commonlogarithm,naturallogarithm,
exponential,andpower
Relationaloperations:<,≤,>,≥,=,and≠
Logicoperations:AND,OR,NOT,andXOR
Statisticaloperations:TLOG(maximum,
minimum,average,sum,P-Pvaluesoftime
seriesdata)orCLOG(maximum,minimum,
average,sum,P-Pvaluesofaspeciedchannel)
Specialoperations:PRE,HOLD,RESET,and
CARRY
Conditionaloperation:[a?b:c]
Bitoperation:BIT
Integerextractingoperation:INT
Remainderextractingoperation:MOD
Trigonometricfunctions:SIN,COS
CP operations: CP.02, CP.CO2
• Computationaccuracy:Double-precisionoating
point
• Datathatcanbeused;
Channeldata:Measurementchannels(0001to
6516to6516),mathematicalchannels(GP10:
A001 to A050, GP20-1: A001 to A100, GP20-2:
A001toA200),Communicationchannels(GP10:
C001 to C050, GP20-1: C001 to C300, GP20-2:
C001toC500),Communicationchannelsraw
data (GP10: RC001 to RC050, GP20-1: C001
to C300,GP20-2: RC001 to RC500),Constants:
K001toK100,Variableconstant:W001toW100,
Internalswitch:S001toS100,Flag:F01toF20,
Recording state (REC01), Integer data: Z000 to
Z999