16
All Rights Reserved. Copyright © 2014, Yokogawa Electric Corporation
GS 04L53B01-01EN May. 19, 2017-00
• KCmarking:Electromagneticwaveinterference
preventionstandard,electromagneticwave
protectionstandardcompliance
*1 Installationcategory(overvoltagecategory)II:
Describesanumberwhichdenesatransient
overvoltagecondition.
Impliestheregulationforimpulsewithstand
voltage.
“II”appliestoelectricalequipmentwhich
issuppliedfromthexedinstallationlikea
distribution board.
*2 Pollution degree 2:
Describesthedegreetowhichasolid,liquid,
or gas which deteriorates dielectric strength or
surfaceresistivityisadhering.
“2”appliestonormalindooratmosphere.
Normally,onlynon-conductivepollutionoccurs.
*3 TheCEstandardsformodulesrepresent
standardsthataremetwhenthemoduleis
installedinthemainunit.
*4 Thisproductisdesignedasopenequipment
undertherelevantstandard,installitasfollows:
•TheGX10/GX20isdesignedtobeinstalledinan
instrumentationpanel.
Install it in a location where people cannot touch
theterminalscarelessly.
•TomaketheGP10/GP20complywiththe
relevantstandard,supportthepartsofthedevice
other than the front-panel control area with an
instrumentationpanelorthelike,andinstallitina
locationwherepeoplecannottouchtheterminals
carelessly or in a panel.
•InstalltheGX60/GMunitinapanelwithadoor.
•Theinstrumentationpanelorpanelusedfor
supportmustcomplywithCSA/UL/EN61010-
2-201ormustbeatleastIP1X(degreesof
protection)andatleastIK09.
• WEEEDirective:Compliant
Construction
• Frontpanel(terminal):Wateranddust-proof,
ComplieswithIEC529-IP20
• Material:Polycarbonate
• Color;
Front:Charcoalgreylight(Munsell10B3.6/0.3
equivalent)
Bezel:Smokeblue(Munsell4.1PB6.0/4.5
equivalent)
• Dimensions:45.2mm(W)x111mm(H)x133.1
mm(D)(D:includingterminalcover)
• Weight:Approx.0.3kg
Power Supply
SuppyfromGX/GP,GX60expandableI/O,GM90PS
powersupplymodule.
• Powerconsumption:1.4Worless
Isolation
Digital output CH1
Digital output CH2
Digital output CH3
Digital output CH4
Digital output CH5
Digital output CH6
Output circuit
Internal circuit
Functional insulation
Reinforced insulation
DIGITAL OUTPUT MODULE (Model
GX90YD, or GX/GP main unit
options /CR1x, /CR2x, /CR4x)
GX90YD
• Application:Alarmoutput,etc
• Numberofoutputs:6
• Outputupdateinterval:100ms(shortest)
• Outputtype:Relaycontactoutput,SPDT(NO-C-
NC)
• Insulationtype:Mechanical
• Ratedloadvoltage:30VDCor250VACorless
• Max.loadcurrent:3A(DC)/3A(AC),resistance
load, each channel
• Min.loadvoltage/current:5VDC/10mA
• Recommendedreplacementperiodsofcontact:
Mechanical5,000,000moreON-OFFoperations
Electrical30,000moreON-OFFoperations(250
VAC3Aor30VDC3A,resistanceload)
• Numberofcommon:6
• Powersupply:Notnecessary
• Terminaltype:M3screwterminal
• Withstandvoltage
Betweentheoutputterminalsandtheinternal
circuit:3000VACforoneminute
Betweentheoutputterminals:3000VACforone
minute
• Insulationresistance:
Betweentheoutputterminalsandtheinternal
circuit:20MΩorgreaterat500VDC
Betweentheoutputterminals:20MΩorgreater
at500VDC
Safety and EMC Standards
• CSA:
CAN/CSA22.2 No.61010-1, installation category
II
*1
, pollution degree 2
*2
CAN/CSA-IEC61010-2-201
*4
• UL:
UL61010-1(CSANRTL/C)
UL61010-2-201(CSANRTL/C)
*4
• CE/EMCdirective
*3
:
EN61326-1compliance,ClassATable2
EN61000-3-2compliance
EN61000-3-3compliance
EN55011 Class A Group 1
• CE/Lowvoltagedirective
EN61010-1
Installation category II
*1
Pollution degree 2
*2
Notincludedinthemeasurementcategory
EN61010-2-201compliance
*4
• EMCRegulatoryArrangementinAustraliaand
NewZealand(RCM):EN55011compliance,
Class A Group 1