EasyManua.ls Logo

York OPTIVIEW YK - Page 100

York OPTIVIEW YK
390 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
100
FORM 160.54-M1
ISSUE DATE: 10/25/2019
SECTION 6 - I/O BOARD
JCI COMPANY CONFIDENTIAL JOHNSON CONTROLS
K11 - Oil Pump Starter (TB 1-29/1) (Style "C"
and earlier chillers)
In automatic operation, contacts close 13 seconds after
System Pre-lube is initiated. Contacts open at completion
of System Coastdown. In manual Oil Pump operation,
the contacts close for the duration of manual pump op-
eration. Anytime the chiller is not in System run or Sys-
tem Coastdown and a motor current value of greater than
15% FLA is detected, the contacts close until motor cur-
rent is no longer detected, whereupon a complete System
Coastdown is performed. If Standby Lubrication is en-
abled, contacts close for 2 minutes every 24 hours since
the oil Pump was last automatically or manually run.
K12 - Oil Return Solenoid (all styles, fixed
or variable speed oil pump). Liquid Line
Solenoid (style D (and later) chillers - J
compressor only, variable speed oil pump)).
Vent line Solenoid (style "C" and earlier
chillers, fixed speed oil pump). (TB1-61)
Contacts close 1 minute after System run is initiated.
They open on chiller shutdown coincident with the be-
ginning of System Coastdown.
With software version C.OPT.01.21.307 (and later), to
avoid an OIL – LOW TEMPERATURE DIFFEREN-
TIAL condition from preventing a chiller start after
running at low load conditions for extended periods,
the solenoid is cycled as follows while the chiller is
running for P, Q and H9 compressors only:
When the Oil Sump Temperature is less than the
Oil Return Min setpoint, close (de-energize) the Oil
Return Solenoid by de-energizing K12 relay.
When the Oil Sump Temperature is greater than
the Oil Return Min setpoint + 7°F, open (ener-
gize) the Oil Return Solenoid by energizing K12
relay.
During coastdown and when not running, the
solenoid operation is not changed from standard
logic, it remains closed.
During startup the operation is not changed from
standard logic, it remains closed for 1 minute af-
ter System run.
K13 - Compressor Motor Starter (start)
(TB1-6/16)
Contacts close coincident with the beginning of Sys-
tem run. They remain closed for 0.2 seconds and then
open.
K14 - Compressor Motor Stop (stop)
(TB 1-6/16)
Contacts close coincident with the beginning of Sys-
tem run. They remain closed for the duration of System
run. They open coincident with the beginning of Sys-
tem Coastdown.
K15 - (TB1 -34/1)Oil Heater (Style D/E all
compressor codes except P; Variable Speed
Oil Pump)
Contacts are open whenever the Oil Pump is operating.
When the Oil Pump is not operating, the contacts are
operated to maintain the Oil Temperature at a target
value of 50°F above the Condenser Saturated Tem-
perature from a minimum of 110°F to a maximum of
160°F. The contacts close when the Oil Temperature
decreases to 4°F below target value; open at 3°F above
the target value.
On Liquid Line Solenoid (Style "C" (and earlier) chillers,
fixed speed oil pump) the contacts function as follows:
On Electromechanical and Solid State Starter ap-
plications the Contacts close 1 minute after Sys-
tem run is initiated.
On Compressor Motor Variable Speed Drive ap-
plications, after the chiller has been running for
greater than or equal to 1 minute the contacts
close if the oil temperature reaches a value greater
than 140°F. They remain closed until the oil tem-
perature decreases to less than 135°F, whereupon
they de-energize.
K16 - High Speed Thrust Solenoid (Style "C"
and earlier chillers; Fixed Speed Oil Pump)
(TB1-62/1)
Contacts close 15 seconds after System run is initiated.
They open on chiller shutdown coincident with the be-
ginning of System Coastdown.
K17 - Condenser Motor Pump Starter (TB1-
164)(If chiller is equipped with Mod B Solid
State Starter, use K5 above)
Contacts operate the same as K14.
K18 - Compressor Motor Starter (TB5-22/25)
Run Status (TB2-35/36)
Contacts operate the same as K14.

Table of Contents

Related product manuals