191
SECTION 21 - TEMPERATURE THERMISTORS
FORM 160.54-M1
ISSUE DATE: 10/25/2019
JOHNSON CONTROLS JCI COMPANY CONFIDENTIAL
21
TABLE 17 - RETURN CHILLED LIQUID TEMPERATURE (HEAT PUMP APPLICATIONS)
TEMP
(°F)
TEMP
(°C)
VIN
0.04 -17.76 1.1353
2.79 -16.23 1.2134
5.44 -14.76 1.2915
8.02 -13.32 1.3696
10.53 -11.93 1.4478
12.98 -10.57 1.5259
15.39 -9.23 1.604
17.75 -7.92 1.6821
20.08 -6.62 1.7603
22.38 -5.34 1.8384
24.66 -4.08 1.9165
26.92 -2.82 1.9946
29.17 -1.57 2.0728
31.41 -0.33 2.1509
33.66 0.92 2.229
TEMP
(°F)
TEMP
(°C)
VIN
35.9 2.17 2.3071
38.15 3.42 2.3853
40.41 4.67 2.4634
42.69 5.94 2.5415
44.99 7.22 2.6196
47.31 8.51 2.6978
49.67 9.82 2.7759
52.06 11.14 2.854
54.49 12.49 2.9321
56.96 13.87 3.0103
59.5 15.28 3.0884
62.1 16.72 3.1665
64.77 18.21 3.2446
67.51 19.73 3.3228
70.35 21.31 3.4009
TEMP
(°F)
TEMP
(°C)
VIN
73.29 22.94 3.479
76.36 24.64 3.5571
79.55 26.42 3.6353
82.89 28.28 3.7134
86.41 30.23 3.7915
90.12 32.29 3.8696
94.07 34.49 3.9478
98.31 36.84 4.0259
102.87 39.37 4.104
107.81 42.12 4.1821
113.26 45.14 4.2603
119.3 48.50 4.3384
126.1 52.28 4.4165
133.93 56.63 4.4946

Table of Contents