EasyManua.ls Logo

York OPTIVIEW YK - Page 204

York OPTIVIEW YK
390 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
204
FORM 160.54-M1
ISSUE DATE: 10/25/2019
SECTION 22 - REMOTE SETPOINTS
JCI COMPANY CONFIDENTIAL JOHNSON CONTROLS
If Analog Remote Mode is selected, the Remote
Analog Input Range setpoint must be set to 0 to 10
VDC or 2 to 10 VDC as detailed below, regardless
of whether the signal is a voltage or current input
signal type.
Microboard Program Jumper JP23 must be posi-
tioned appropriately per the input signal type as
detailedbelow.Itisrecommendedthataqualied
Service technician position this jumper.
IMPORTANT! - The signal type used for
Remote Current Limit setpoint reset and
the signal type used for Remote Leaving
Chilled Liquid Temperature setpoint reset
must be the same. For example, if a 0 to
10 VDC signal is being used for Remote
Leaving Chilled Liquid Temperature
Reset, then a 0 to 10 VDC signal must
be used for Remote Current Limit Reset.
0 to 10 VDC
As shown in Figure 30 on page 94, connect input
to Microboard J22-1 (signal) and J22-5 (GND). The
setpoint varies linearly from 100% to 30% FLA as the
input varies from 0 to l0 VDC. This input will only be
accepted when Analog Remote Mode is selected, the
Remote Analog Input Range setpoint is set for 0 to 10
VDC and Microboard Program Jumper JP23 has been
removed. Calculate the setpoint for various inputs as
follows:
Setpoint (%) = 100 – ( VDC x 7)
For example, if the input is 5 VDC, the setpoint would
be set to 65% as follows:
Setpoint (%) = 100 – (5 x 7)
= 100 – 35
= 65%
2 to 10 VDC
As shown in Figure 30 on page 94, connect input
to Microboard J22-1 (signal) and J22-5 (GND). The
setpoint varies linearly from 100% to 30% FLA as the
input varies from 2 to 10 VDC. This input will only be
accepted when Analog Remote Mode is selected, the
Remote Analog Input Range setpoint is set for 2 to 10
VDC and Microboard Program Jumper JP23 has been
removed. Calculate the setpoint for various inputs as
follows:
Setpoint (%) = 100 – [( VDC – 2) x 8.75]
For example, if the input is 5 VDC, the setpoint would
be set to 74% as follows:
Setpoint (%) = 100 – [(5 - 2) x 8.75]
= 100 – [3 x 8.75]
= 100 – 26.25
= 74%
0 to 20mA
As shown in Figure 30 on page 94, connect input
to Microboard J22-2 (signal) and J22-5 (GND). The
setpoint varies linearly from 100% to 30% FLA as the
input varies from 0mA to 20mA. This input will only
be accepted when Analog Remote Mode is selected,
the Remote Analog Input Range setpoint is set for 0
to 10 VDC and Microboard Program Jumper JP23 has
been placed on pins 1 and 2. Calculate the setpoint for
various inputs as follows:
Setpoint (%) = 100 – (mA x 3.5)
For example, if the input is 8mA, the setpoint would be
set to 72% as follows:
Setpoint (%) = 100 – (8 x 3.5)
= 100 – 28
= 72%
4 to 20mA
As shown in Figure 30 on page 94, connect input
to Microboard J22-2 (signal) and J22-5 (GND). The
setpoint varies linearly from 100% to 30% FLA as the
input varies from 4mA to 20mA. This input will only
be accepted when Analog Remote Mode is selected,
the Remote Analog Input Range setpoint is set for 2
to 10 VDC and Microboard Program Jumper JP23 has
been placed on pins 1 and 2. Calculate the setpoint for
various inputs as follows:
Setpoint (%) = 100 – [(mA – 4) x 4.3 75]
For example, if the input is 8mA, the setpoint would be
set to 83% as follows:
Setpoint (%) = 100 – [(8–4) x 4.375]
= 100 – (4 x 4.375)
= 100 – 17.5
= 82.5
= 83%

Table of Contents

Related product manuals