EasyManua.ls Logo

York OPTIVIEW YK - Page 209

York OPTIVIEW YK
390 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
209
SECTION 22 - REMOTE SETPOINTS
FORM 160.54-M1
ISSUE DATE: 10/25/2019
JOHNSON CONTROLS JCI COMPANY CONFIDENTIAL
22
perature Range setpoint). Select Analog Remote Mode.
The Remote Analog Input Range setpoint must be set
to 2 to 10 VDC and Microboard JP24 must be placed
on pins 1 and 2. The setpoint is calculated as follows:
Offset (°F) = (mA-4)(Remote Reset Temp Range)
16
Setpoint(°F) = Local Setpoint – Offset
PWM
The Pulse Width Modulation input is in the form of a
1 to 11 second relay contact closure that applies 115
VAC to the I/O Board TB4-19 for 1 to 11 seconds. As
shown in Figure 34 on page 102, connect dry closure
contacts between I/O Board TB4-19 (signal) to TB4-1
(115 VAC). A 1 second closure produces a 0°F offset.
An 11 second closure produces the maximum allowed
offset above the Local Setpoint (as allowed by the Re-
mote Reset Temperature Range setpoint). Select Digital
Remote Mode. The relay contact closure should occur
at least once every 30 minutes to maintain the setpoint
to the desired value. If a contact closure is not received
within 30 minutes of the last closure, the setpoint is
defaulted to the Local setpoint value. A closure is only
accepted at rates not to exceed once every 70 seconds.
The setpoint is calculated as follows:
10
Offset(°F) =
(PW – 1)(Remote Reset Temp Range)
Where PW = Pulse Width in seconds
Setpoint (°F) = Local Setpoint - Offset
RS-232
As shown in Figure 29 on page 93, a setpoint can
be received in serial form at the microboard COM4B
serial port (J2) from the E-Link Gateway. Select ISN
Remote Mode.

Table of Contents

Related product manuals