EasyManua.ls Logo

York OPTIVIEW YK - Page 334

York OPTIVIEW YK
390 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
334
FORM 160.54-M1
ISSUE DATE: 10/25/2019
SECTION 36 - SOFTWARE ENHANCEMENTS
JCI COMPANY CONFIDENTIAL JOHNSON CONTROLS
SI0006 - SOFTWARE ENHANCEMENTS EFFECTIVE MAY 2001 (CONT'D)
COMPRESSOR MOTOR VARIABLE SPEED
DRIVE
1. The compressor motor Variable Speed Drive
(VSD) Phase A, B and C output current to the mo-
tor is now displayed on the VSD TUNING screen.
2. The new 351HP VSD is supported. In this model,
the three inverter assemblies are mounted on a
single baseplate instead of three individual heat
sink assemblies like other models. Therefore, the
VSD DETAILS screen and the HARMONIC FIL-
TER DETAILS screen display a single baseplate
temperature instead of the Phase A, B and C tem-
peratures displayed on other models.
OIL PUMP VARIABLE SPEED DRIVE
In previous flash memory card versions, the oil pump
VSD starts at 25Hz when turned on during System Pre-
lube. In this version, the VSD starts at 45Hz, which
provides greater reliability in achieving the required 45
psid target oil pressure at chiller start.