387
SECTION 36 - SOFTWARE ENHANCEMENTS
FORM 160.54-M1
ISSUE DATE: 10/25/2019
JOHNSON CONTROLS JCI COMPANY CONFIDENTIAL
36
SI0300 - SOFTWARE ENHANCEMENTS (VER 27) EFFECTIVE JUNE 2015 (CONT'D)
E-LINK CODE ADDITIONS
The following new code definitions have been added in
this software release and is compatible with the E-Link
data table for YK OptiView BAS (Rev K_04a).
E-LINK CODE ADDITIONS
UNIT SAFETY FAULT CODES
CODE DESCRIPTION
15 Motor - Lack of Motor Oil Change
UNIT CYCLING FAULT CODES
CODE DESCRIPTION
69 Motor Auto Lubrication In Progress
UNIT WARNING CODES
19 Warning – Auto Lube Req’d On Next Shutdown
20 Warning – Auto Lube Grease Level Low
21 Warning – Auto Lube Failed
22 Warning – Motor Oil Change Suggested
23 Warning – Motor Oil Change Required
24 Warning – Lack of Motor Oil Change
LANGUAGES
The panel now supports Turkish.
LCHWT REMOTE RESET
When a BAS system changes the LCHWT setpoint up
more than the Low Water Temperature Offset the chill-
er controller with v.24 software and later, the chiller
control should have ramped the new setpoint up from
the old setpoint at the rate of 0.2°F per second to al-
low the chiller to unload and not cause a LWT shut-
down. This did not work properly and was fixed in this
v.27/v.0 release.

Table of Contents