User’s Manual 1PH HYD3000-HYD6000-ZSS
Rev. 1.1 16/03/2021
Identification: MD-AL-GI-00
Rev. 1.1 of 16/03/2021 - Application: GID
The 1PH HYD3000-HYD6000-ZSS inverter
receives a remote signal to decrease its
power.
Remote shutdown of HYD
inverters
The 1PH HYD3000-HYD6000-ZSS inverter
receives a remote signal to shutdown.
SOC <= 1 -DOD
or
The battery voltage is low
Battery voltage is lower
than the DOD
For example, if the DOD is set at 30%, when
the DOD is below 70%, ID85 will appear in
the event list.
The 1PH HYD3000-HYD6000-ZSS inverter
will not discharge the battery when ID85 is
present.
Or, it could indicate that the battery voltage
is too low. In this case, the 1PH HYD3000-
HYD6000-ZSS inverter will not discharge the
battery to ensure a longer battery life.
Check whether the photovoltaic and grid
conditions meet the charging conditions.
Software version is not
consistent
The firmware version
installed is not suitable
for the type of inverter.
Contact Technical Support to update the
software.
The EEPROM
communication board is
faulty.
ID95-ID96 are internal faults of the 1PH
HYD3000-HYD6000-ZSS inverter; switch it
off, wait 5 minutes and then switch it back on
again. Check if the problem has been resolved.
If not, contact ZCS Technical Support.
The RTC clock chip is
faulty.
ID98 is generally caused by a loose SD card
support. Click and pull out the SD card, press
the support and reinsert the card. This should
fix the problem.
Contact Technical Support
Battery discharge
overcurrent protection
ID100-ID103 are battery errors. If the alarm
occurs occasionally, wait a few moments to
see if the problem has been resolved.
If the fault occurs frequently, contact ZCS
Short-circuit discharge
protection