Technical Data of the complete device
Data Value
Process voltage:
-> Connections X4/L+ (pin 20), X4/L+ (pin 21), X4/M (pin 22),
X4/M (pin 23)
-> Fuse for L+ 10 A, fast acting
- Electrical isolation No
Current consumption:
-> via L+ 0.19 A + output load
- Inrush current via L+ (when voltage is
switched on)
0.18 A²s
Power consumption Replacement device: 9 W
Existing device: 5 W
For further information, please refer to the existing documentation
System description Advant Controller 31.
CAUTION!
System damage caused by voltage!
Exceeding the maximum supply or process voltage (>30 V DC) results in per-
manent system damage (destruction).
Technical Data of the binary input
Data Value
Input current at input voltage +24 V Typ. 6 mA
Protection against reversed voltage Yes
Overvoltage protection No
The enabling input is a proprietary input.
For further information, please refer to the existing documentation
System description Advant Controller 31.
AC31 Adapters
Replacement devices: I/O modules > Replacement device 07AC91-AD
2018/09/243ADR010122, 8, en_US118